Wall Mount CO2 Sensor,with no display,0/2-10Vdc or 0/4-20mA output.
Overview
These stand-alone Carbon Dioxide (CO2) Sensors and Controllers are used for determining ventilation necessity with HVAC controllers and to manage the amount of fresh outdoor air supplied to maintain acceptable levels of CO2 in the space.
Features
Models available with LCD that provides sensor readings and status information.
Non-Dispersion-Infrared (NDIR) technology used to measure carbon dioxide gas.
Gold-plated sensor provides long-term calibration stability.
C7232 provides voltage or current output based on CO2 levels.
SPST relay output.
Used for CO2 based ventilation control (Demand Control Ventilation (DCV)).
Automatic Background Calibration (ABC) algorithm based on long-term evaluation reduces required typical zero-drift check maintenance.
Product Specifications
Application
Carbon Dioxide Sensor
Dimensions (in.)
5 1/16 in. high x 3 5/32 in. wide x 2 in. deep
Dimensions (mm)
128 mm high x 80 mm wide x 25 mm deep
Includes
No Honeywell Logo
Item Type
Product
Mounting
Wall mount
Frequency
50 Hz; 60 Hz
Electrical Connections
Six leadwires, 20-gauge, 6 in. long
Sensor
Non-dispersive Infrared (NDIR)
Contact Ratings
1 A @ 50 Vac/24 Vdc
Voltage
24 Vac/dc �20%,
Operating Temperature Range (F)
32 F to 122 F
Operating Temperature Range (C)
0 C to 50 C
Relay Outputs
One: Normally Open SPST
Timing
Response--1 minute
Accuracy
5% full scale
Display
None
Sensor Range
0 to 2000 ppm, adjustable
Analog Current Output
0/2 - 10 Vdc or 0/4 - 20 mA selectable, w/ one relay output
Related Units, Accessories, And OEM Replacement Parts