Emerson 059542 is a 48 cubic inch Model H48 Filter Drier Core. This is used for High Acid and Water Removal and the recommendable refrigerants are CFC and HCFC Refrigerants.
Emerson Filter Cores are applicable for use in ADKS and STAS shells. They have exceptional acid capacities for normal system protection, or to effectively clean-up following a compressor burnout. Features water capacities to suit specific system conditions.
Â
NOTE: Filter Drier cores are suitable for use with R-11 AND R-123 but filters are NOT. May not be used for BTAS.
Â
FILTER DRIER WATER CAPACITY:
Â
Model No.
Water Capacity Drops of Water
 059542
H48
R-12
R-134a
R-22
R-407C
R-404A/R-507
R410A
R-502
75°F
125°F
75°F
125°F
75°F
125°F
75°F
125°F
75°F
125°F
75°F
125°F
75°F
125°F
1020
688
676
538
597
436
445
285
721
535
380
226
643
475
Water Capacities are based on Equilibrium Point Dryness (EPD):
50 parts per million for R-134a, R404-A/R-410A R-407C
60 parts per million for R-22
15 parts per million for R-12