Description:
TeSys K Mini IEC Non-Reversing Contactor (6A Inductive/15A Resistive, 24V Coil, 3P)
Specifications:
Range: TeSys
Product or Component Type: Contactor
Device Application: Control
Contactor Application: Motor Control
Utilisation Category: AC-4, AC-3
Poles: 3
Power Pole Contact Composition: 3 NO
[Ue] Rated Operational Voltage: Power Circuit 690 V AC 50/60 Hz, Signalling Circuit <= 690 V AC 50/60 Hz
[Ie] Rated Operational Current: 6 A<= 440 V AC AC-3 Power Circuit
Control Circuit Type: AC 50/60 Hz
[Uc] Control Circuit Voltage: 24 V AC 50/60 Hz
Motor Power kW: 1.5 kW 220...230 V AC 50/60 Hz AC-3, 2.2 kW 380...415 V AC 50/60 Hz AC-3, 3 kW 440 V AC 50/60 Hz AC-3, 3 kW 480 V AC 50/60 Hz AC-3, 3 kW 500...600 V AC 50/60 Hz AC-3, 3 kW 660...690 V AC 50/60 Hz AC-3, 1.5 kW 400 V AC 50/60 Hz AC-4
Auxiliary Contact Composition: 1 NO
[Uimp] Rated Impulse Withstand Voltage: 8 kV
Overvoltage Category: III
[Ith] Conventional Free Air Thermal Current: 20 A 122 °F (50 °C) Power Circuit, 10 A 122 °F (50 °C) Signalling Circuit
Irms Rated Making Capacity: 110 A AC Power Circuit NF C 63-110, 110 A AC Power Circuit IEC 60947, 110 A AC Signalling Circuit IEC 60947
Rated Breaking Capacity: 110 A 415 V IEC 60947, 110 A 440 V IEC 60947, 80 A 500 V IEC 60947, 110 A 220...230 V IEC 60947, 110 A 380...400 V IEC 60947, 70 A 660...690 V IEC 60947
[Icw] Rated Short-Time Withstand Current: 90 A 122 °F (50 °C) - 1 s Power Circuit, 85 A 122 °F (50 °C) - 5 s Power Circuit, 80 A 122 °F (50 °C) - 10 s Power Circuit, 60 A 122 °F (50 °C) - 30 s Power Circuit, 45 A 122 °F (50 °C) - 1 min Power Circuit, 40 A 122 °F (50 °C) - 3 min Power Circuit, 20 A 122 °F (50 °C) - >= 15 min Power Circuit, 80 A - 1 s Signalling Circuit, 90 A - 500 ms Signalling Circuit, 110 A - 100 ms Signalling Circuit
Associated Fuse Rating: 25 A gG <= 440 V Power Circuit, 25 A aM Power Circuit, 10 A gG Signalling Circuit IEC 60947, 10 A gG Signalling Circuit VDE 0660
Average Impedance: 3 mOhm - Ith 20 A 50 Hz Power Circuit
[Ui] Rated Insulation Voltage: Power Circuit 600 V UL 508, Power Circuit 690 V IEC 60947-4-1, Signalling Circuit 690 V IEC 60947-4-1, Signalling Circuit 690 V IEC 60947-5-1, Signalling Circuit 600 V UL 508
Power Circuit 600 V CSA C22.2 No 14, Signalling Circuit 600 V CSA C22.2 No 14
Insulation Resistance: > 10 MOhm signalling circuit
Inrush Power in VA: 30 VA 68 °F (20 °C)
Hold-in Power Consumption in VA: 4.5 VA 68 °F (20 °C)
Heat Dissipation: 1.3 W
Control Circuit Voltage Limits: Operational 0.8...1.15 Uc 122 °F (50 °C), Drop-out 0.2...0.75 Uc 122 °F (50 °C)
Connections - Terminals: Screw Clamp Terminals 1 0.00…0.01 in² (1.5…4 mm²) Solid, Screw Clamp Terminals 1 0.00…0.01 in² (0.75…4 mm²) Flexible without Cable End, Screw Clamp Terminals 1 0.00…0.00 in² (0.34…2.5 mm²) Flexible with Cable End, Screw Clamp Terminals 2 0.00…0.01 in² (1.5…4 mm²) Solid, Screw Clamp Terminals 2 0.00…0.01 in² (0.75…4 mm²) Flexible without Cable End, Screw Clamp Terminals 2 0.00…0.00 in² (0.34…1.5 mm²) Flexible with Cable End
Maximum Operating Rate: 3600 cyc/h
Auxiliary Contacts Type: Instantaneous 1 NO
Signalling Circuit Frequency: <= 400 Hz
Minimum Switching Current: 5 mA Signalling Circuit
Minimum Switching Voltage: 17 V Signalling Circuit
Mounting Support: Rail, Plate
Tightening Torque: 11.51 lbf.in (1.3 N.m) Screw Clamp Terminals Philips No 2, 11.51 lbf.in (1.3 N.m) Screw Clamp Terminals Flat Ø 6 mm
Operating Time: 10...20 ms Coil De-energisation and NO Opening, 10...20 ms Coil Energisation and NO Closing
Mechanical Durability: 10 Mcycles
Electrical Durability: 1.3 Mcycles 6 A AC-3 <= 440 V
Ambient Air Temperature for Storage: -58…176 °F (-50…80 °C)
Operating Altitude: 6561.68 ft (2000 m) Without
Flame Retardance: V1 UL 94, Requirement 2 NF F 16-101, Requirement 2 NF F 16-102
Warranty: 18 Months