Flame Sensor, Ultraviolet, Minipeeper.
Overview
Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers.
Features
Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection.
C7027 mounts on a 1/2 in. sighting pipe by using an integral collar.
Detectors can be wired in parallel for difficult sighting applications.
C7027 seals against pressures up to 5 psi (34.5kPa) when correctly installed.
Allows for blast tube mounting due to compact size.
C7044 mounts with a two screw bracket.
The C7044 UV sensor tube is enclosed in a stainless steel housing.
C7044 has the capability of side or end viewing in flame monitoring applications.
Product Specifications
Application
Coal fired burners; Gas fired burners; Oil fired burners
Dimensions (in.)
1 1/16 in. diameter x 4 in. long
Dimensions (mm)
27 mm diameter x 102 mm long
Used With
Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290
Comments
Detects ultraviolet radiation in flames
Mounting
Integral nut for 1/2 in. sighting pipe.
Approvals, Underwriters Laboratories Inc.
Listed: File No. MP268, Guide No. MCCZ
Approvals, Canadian Standards Association
Certified: Master Report LR95329-1
Electrical Connections
2 NEC Class 1 lead wires
Vibration
0.5 G max
Approvals, Swiss RE
Acceptable
Approvals, Factory Mutual
Approved: Report No. 24181.03
Type
Ultraviolet, Minipeeper
Ambient Temperature Range (F)
0 F to 215 F
Ambient Temperature Range (C)
-18 C to +102 C
Approvals, Others
DIN (Europe)
Lead Length (in.)
96 in.
Lead Length (mm)
2438 mm